Instrumentation, Process Control & Automation in ICAR AICE-JRF/SRF

Measuring and controlling temperature, flow, pressure and level in a milk plant, from sensors to PLC and SCADA.

Our 108 ICAR AICE-JRF/SRF questions in this subject: 33 easy, 54 medium, 21 hard, across 10 units.

10 practice questions, worked

Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.

These 10 were written to ICAR AICE-JRF/SRF and are not shown on any other exam's page.

Question 1 · hard

A 12-bit analogue-to-digital converter digitises a 0–150 °C range. What is the approximate temperature resolution?

  1. About 0.15 °C
  2. About 0.037 °C
  3. About 0.59 °C
  4. About 0.012 °C
Answer and working

B. About 0.037 °C

A 12-bit converter has 2^12 = 4,096 steps: 150 ÷ 4,096 ≈ 0.037 °C. 0.59 °C is the 8-bit value (150 ÷ 256); 0.15 °C divides by 1,000; 0.012 °C divides by 12,288, which is not a converter size.

Question 2 · easy

In CIP, return-line conductivity is mainly used to:

  1. Measure the flow velocity in the return pipe
  2. Measure the residual protein film on surfaces
  3. Count the number of cleaning cycles
  4. Detect the change between rinse water and detergent
Answer and working

D. Detect the change between rinse water and detergent

Detergents conduct far more than water, so the return conductivity shows when full-strength detergent arrives and when rinse water replaces it. It does not measure soil films, cycle counts or velocity.

Question 3 · easy

A controller's proportional band is 25%. What is its gain?

  1. 0.25
  2. 4
  3. 400
  4. 25
Answer and working

B. 4

Gain = 100 ÷ PB = 100 ÷ 25 = 4. 0.25 is PB as a fraction; 25 is PB itself; 400 multiplies instead of dividing.

Question 4 · easy

Why does a proportional-only temperature controller leave an offset after a change in milk flow?

  1. It responds only to the rate of change of temperature
  2. Its gain falls automatically as the load increases
  3. A non-zero error is needed to hold the valve at its new opening
  4. Its derivative term cancels the integral term at steady state
Answer and working

C. A non-zero error is needed to hold the valve at its new opening

With P-only control, output changes only when there is error, so a new steady load needs a steady error. P-only has no integral or derivative terms, its gain is fixed, and it responds to error, not rate.

Question 5 · medium

What is the main idea of the ISA-88 batch-control standard?

  1. Setting the accuracy class of pasteuriser recording thermometers
  2. Defining the colours and sounds used for alarms on operator screens
  3. Specifying cybersecurity zones and conduits for plant control networks
  4. Recipes say what to make; equipment control says how, kept separate
Answer and working

D. Recipes say what to make; equipment control says how, kept separate

ISA-88 models recipes and equipment separately, so equipment phases can be reused by many recipes. Cybersecurity is IEC 62443; recorder accuracy is regulatory; screen colours are a design guideline.

Question 6 · easy

What distinguishes a distributed control system (DCS) from a PLC-plus-SCADA system?

  1. A DCS cannot handle analogue signals such as temperature or pressure at all
  2. A DCS works only for batch processes and never for continuous ones like UHT
  3. One integrated platform supplies controllers, I/O, stations and tools
  4. A DCS uses no programmable controllers at any level of the system hierarchy
Answer and working

C. One integrated platform supplies controllers, I/O, stations and tools

A DCS integrates its control, I/O and operator layers in one system, traditionally for large continuous plants. It uses controllers, handles analogue signals and suits continuous processes.

Question 7 · medium

A CIP detergent tank holds 2,000 L of water to be made up to 1.5% w/v sodium hydroxide using a 50% w/w caustic solution. Ignoring the volume added, how much 50% solution is needed?

  1. 120 kg
  2. 30 kg
  3. 15 kg
  4. 60 kg
Answer and working

D. 60 kg

NaOH needed = 2,000 L × 15 g/L = 30 kg; as 50% solution: 30 ÷ 0.5 = 60 kg. 30 kg is the pure NaOH; 15 kg halves again; 120 kg divides by 0.25.

Question 8 · easy

Why is an air eliminator fitted ahead of the reception flowmeter?

  1. So entrained air is not measured and paid for as milk
  2. So the milk is cooled before it reaches the silo
  3. So the tanker empties faster through a wider pipe
  4. So foam is added to protect the milk from oxygen
Answer and working

A. So entrained air is not measured and paid for as milk

Air bubbles occupy volume in the meter and would be counted as milk, overpaying the supplier. The air eliminator does not cool, speed unloading or add foam.

Question 9 · medium

A magnetic flowmeter records 12,000 L of milk at reception. Taking density as 1.030 kg/L, what mass is credited?

  1. 12,000 kg
  2. 12,360 kg
  3. 12,036 kg
  4. 11,650 kg
Answer and working

B. 12,360 kg

Mass = 12,000 × 1.030 = 12,360 kg. 11,650 kg divides by density; 12,000 kg ignores density; 12,036 kg uses 1.003.

Question 10 · hard

Why must interlocks that keep CIP solution out of product lines use valve-position feedback rather than the valve command alone?

  1. A stuck valve ignores its command; only feedback proves the route is closed
  2. Feedback switches are needed only to measure the flow rate through the valve
  3. Valve commands are not recorded by the PLC, so they cannot be checked later
  4. Feedback lets the operator open and close the valve directly from the screen
Answer and working

A. A stuck valve ignores its command; only feedback proves the route is closed

A command shows what the PLC asked for, not what happened; a stuck valve could let caustic reach product. Feedback switches confirm actual position. Commands are recorded, feedback does not measure flow, and screen control is not the point.

A study plan for Instrumentation, Process Control & Automation in ICAR AICE-JRF/SRF

This plan follows where our questions actually fall, so the time goes where the marks are likely to be. It is our reading of the syllabus, not the exam body's weighting.

  1. First, the heavy units (43% of the 108 questions): Control modes: on-off, P, PI and PID (12, 11%); Temperature measurement: thermocouples, RTDs and recorders (12, 11%); Automation of pasteurisers, CIP and milk reception (11, 10%); Final control elements: valves and drives (11, 10%).

    Read the manual chapters for these first and do every worked question you can find on them.

  2. Then the middle band: Generalised measurement system and instrument characteristics (11, 10%); pH, conductivity and inline composition sensors (11, 10%); Pressure, flow and level measurement (11, 10%); Data integrity and electronic records (10, 9%).

    Aim for one sitting per unit, then mixed questions across them.

  3. Then the lighter units: Programmable logic controllers (10, 9%); SCADA and distributed control systems (9, 8%).

    Learn the definitions, classifications and standard numbers; these units are more often recalled than worked.

  4. Leave time for the hard ones: pH, conductivity and inline composition sensors (3 hard of 11), Control modes: on-off, P, PI and PID (3 hard of 12), Temperature measurement: thermocouples, RTDs and recorders (3 hard of 12).

    Come back to these after a first pass, untimed, and read every explanation, including for the options you rejected.

  5. Bank the easy marks: Generalised measurement system and instrument characteristics (4 easy of 11); Control modes: on-off, P, PI and PID (4 easy of 12).

    Do these early in revision so they are fast on the day.

  6. Finish timed. Sit the subject as a timed set without notes, mark it, and send each wrong answer back to its unit above.

Last updated · How Laisha writes and checks its pages · Report a mistake

Ask Laisha about this

Opens Laisha's chat with your question ready to send. Sign in or start free.

Unlock every question — ICAR AICE-JRF/SRF Instrumentation, Process Control & Automation

US$10 a month · one price worldwide · cancel any time

  • Every practice question in this subject, with full working
  • Timed exam papers and progress by unit
  • Ask Laisha to explain any answer — up to 1,000 questions a month
Free or Smarter
FreeSmarter
Grow guides, pest pages, articlesRead allRead all
Ask Laisha5 a dayUp to 1,000 a month
Exam practiceThe sample on each pageEvery question, timed papers
Crop calendar and pest alerts—For your own fields
Calculators and tools—All
Uploads and reports—100 a month, real files
10 days free for every new account, no card.