Original practice questions written to the published syllabus · not past papersICAR AICE-JRF/SRF (PhD) — Agricultural Engineering subjects 38–43 is a PhD, fellowship and lectureship exam run by National Testing Agency for ICAR, for candidates in India. LAN-based computer test, 2 hours, 120 MCQs: 20 Part A (general knowledge and reasoning), 50 Part B (core group), 50 Part C (specialisation); four options.
Source: icar.org.in.
Checked against the exam body's published information. Formats and fees change; confirm the current edition there before you book.
Subject 38 Unit 6 (refrigeration) and subject 41's storage engineering unit go to PG depth: multistage and cascade systems, volumetric efficiency, absorption COP limits, refrigerant transition under the Kigali Amendment, ice-bank sizing for milk, Plank's equation and its assumptions, and cold-store design choices such as evaporator TD and humidity.
Refrigeration cycles, equipment and cold-store design, from COP to the heat load of a room full of potatoes.
Our 31 ICAR AICE-JRF/SRF questions in this subject: 0 easy, 12 medium, 19 hard, across 14 units.
Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.
These 10 were written to ICAR AICE-JRF/SRF and are not shown on any other exam's page.
An ideal absorption refrigerator receives heat at 100 °C, rejects heat to surroundings at 30 °C and refrigerates at -10 °C. Its maximum possible COP is about
B. 1.23
COP_max = [(T_G − T_0)/T_G] × [T_E/(T_0 − T_E)] = (70/373.15) × (263.15/40) = 0.1876 × 6.579 = 1.23. 6.58 is only the Carnot refrigerator part and 0.19 only the engine part; 0.18 uses Celsius temperatures ((70/100) × (10/40) = 0.175).
A carbon dioxide (R-744) refrigeration system in a hot climate usually operates transcritically because
D. Its critical temperature of 31 °C is below usual heat-rejection temperatures
Above the critical temperature no condensation occurs, so heat is rejected in a gas cooler at supercritical pressure. Its critical pressure is high (about 74 bar), not low.
For a reciprocating compressor with clearance ratio 0.05 and re-expansion index 1.2, the pressure ratio at which the clearance volumetric efficiency falls to zero is about
D. 38.6
Set 1 + C − C r^(1/n) = 0: r = ((1 + C)/C)^n = (21)^1.2 = 38.6. Forgetting the exponent gives 21; using 1/n gives 12.6. In practice staging is used long before this ratio. 20.0 is 1/C, forgetting both the (1 + C) and the exponent.
1000 kg of fish (water content 70%) at 5 °C is frozen to -18 °C; initial freezing point -2 °C. Using Siebel's c_p = 3.35x_w + 0.84 above and 1.26x_w + 0.84 below freezing, and L = x_w × 334 kJ/kg, the heat removed is about
B. 284 MJ
c_p above = 3.185, below = 1.722 kJ/kg K, L = 233.8 kJ/kg. Q = 1000×[3.185×7 + 233.8 + 1.722×16] = 1000×[22.3 + 233.8 + 27.6] = 283,647 kJ ≈ 284 MJ. Using 334 kJ/kg for the product ignores that only the water freezes; latent alone gives 234 MJ; 73 MJ uses the unfrozen c_p over the whole 23 K drop and ignores the phase change. 384 MJ uses L = 334 kJ/kg (22.3 + 334 + 27.6); 73 MJ is 3.185 × 23 K.
Spherical fruit pieces of diameter 6 cm (ρ = 1050 kg/m³, L = 280 kJ/kg, freezing point -1.0 °C, frozen k = 1.2 W/m K) are frozen in air at -25 °C with h = 25 W/m² K. Plank's equation gives a freezing time of about
C. 1.79 h
Sphere: P = 1/6, R = 1/24, a = diameter. ρL/ΔT = 12,250,000. Bracket = 0.06/150 + 0.0036/28.8 = 0.000400 + 0.000125 = 0.000525. t = 6,431 s = 1.79 h. Slab constants give 5.36 h and cylinder constants 2.68 h; using the radius gives 0.79 h.
Moisture that enters cold-store insulation is harmful mainly because
A. Water and ice conduct heat far better than trapped gas, so insulation value falls and ice builds up
Liquid water conducts heat roughly twenty times better than still air and ice more still; condensation freezes in the cold layers and builds up because the vapour drive is nearly one-way. Weight is a secondary effect.
Pressure-relief ports are fitted in the walls of sealed freezer rooms because
B. Air contracts on cooling and expands during defrost, creating pressure differences that can damage panels
A freezer room is nearly airtight; cooling of admitted warm air produces a vacuum and heating during defrost a positive pressure, either of which can distort or burst panels and make doors hard to open. The ports are heated to prevent icing.
A daily milk-cooling load of 241,800 kJ arrives once a day. Compare the average refrigeration capacity needed if an ice bank is built over 10 h with that needed to cool the milk directly in 2 h.
D. 6.7 kW with ice bank against 33.6 kW direct
Ice bank: 241,800/(10 × 3,600) = 6.72 kW. Direct: 241,800/(2 × 3,600) = 33.6 kW. The ice bank lets a compressor about one-fifth the size do the job, at the cost of a lower evaporating temperature. The second option has TR values labelled as kW.
For a village milk-collection centre with an unreliable daytime grid supply, the main engineering reason to choose an ice-bank cooler over a direct-expansion bulk cooler is that
D. Cooling is stored while power is available and released at milking, without a large compressor running then
The ice bank decouples compressor running from the milk-cooling peak. Direct-expansion coolers are more energy-efficient because they evaporate at a higher temperature, so that option describes the DX cooler, not the ice bank. Neither should freeze milk.
In controlled-atmosphere storage of apples, lowering oxygen too far below the tolerance limit of the cultivar causes
A. Anaerobic respiration with alcohol and off-flavour production
CA slows aerobic respiration by lowering O2 and raising CO2, but below the lower oxygen limit the fruit switches to fermentation, producing ethanol and acetaldehyde. Ethylene synthesis is actually suppressed by low O2.
This plan follows where our questions actually fall, so the time goes where the marks are likely to be. It is our reading of the syllabus, not the exam body's weighting.
Read the manual chapters for these first and do every worked question you can find on them.
Aim for one sitting per unit, then mixed questions across them.
Learn the definitions, classifications and standard numbers; these units are more often recalled than worked.
Come back to these after a first pass, untimed, and read every explanation, including for the options you rejected.
Last updated · How Laisha writes and checks its pages · Report a mistake
US$10 a month · one price worldwide · cancel any time
| Free | Smarter | |
|---|---|---|
| Grow guides, pest pages, articles | Read all | Read all |
| Ask Laisha | 5 a day | Up to 1,000 a month |
| Exam practice | The sample on each page | Every question, timed papers |
| Crop calendar and pest alerts | — | For your own fields |
| Calculators and tools | — | All |
| Uploads and reports | — | 100 a month, real files |
An AI operating system for agriculture: free guides, manuals and tools written for every country.